Distribution
Pulsar - TECHNICAL CHARACTERISTICS
« back to Distribution
Rear view of Pulsar "Hot-swap" version
Flexibility of connections
Pulsar offers different connection possibilities:
Plug-in ("Fault-tolerant" and " Hot-swap" versions) for direct connection
"Fault-tolerant" version
"Hot-swap" version
|
Terminal blocks ("Install version") for installations in an electronical environment.
"Install" version
|
Characteristics
| Pulsar |
700 C |
1000 C |
1500 C |
| General |
| Power (Pn) |
700 VA /490 W |
1000 VA /700 W |
1500 VA /1050 W |
| Input-voltage range |
120/140/160 to 276 volts without using battery power (1) |
| Frequency range |
50/60 Hz (auto-selection) |
| Power factor (THDI) |
> 0.95 (< 5%) |
| Sinusoidal output voltage |
200/208/220/230/240 Volts |
| Harmonic distortion |
< 4% on linear load,< 6% on non-linear load |
| Efficiency |
85% |
87% |
88% |
| Crest factor |
3:1 |
3:1 |
3:1 |
| Short circuit current (A) |
25 |
29 |
29 |
| Overload capacity (Online mode) |
110%permanent,130%12s,>130%1,5s |
| Batteries |
| backup time |
100%Pn 50%Pn |
100%Pn 50%Pn |
100%Pn 50%Pn |
| Standard |
7 14 |
7 17 |
6 19 |
| Pulsar C +1 Pulsar EXB |
NA NA |
27 59 |
24 79 |
| Pulsar C +1 Pulsar EXB |
NA NA |
48 93 |
43 119 |
| Pulsar C +3 Pulsar EXB |
NA NA |
64 136 |
62 168 |
| Automatic battery test |
Yes,at regular intervals without risk of interrupting protected applications |
| Communication |
| USB port |
yes |
yes |
yes |
| RS232 port |
yes |
yes |
yes |
| Optional cards |
SNMP/Web card - status information card |
| Environment |
| Acoustic noise |
< 40 dBA |
| Operating temperature |
0 to 40°C |
| Standards and certifications |
| Performance |
EN 50091-3/IEC 62040-3 |
| Performance |
EN 50091-3/IEC 62040-3 |
| Safety |
EN 50091-1,EN 60950 (RD/),IEC 60950 |
| EMC |
EN 50091-2/IEC 62040-2,EN 55022/B,FCC 47 part 15 -Subpart B -Class A, IEC 61000-4-2/-3/-4/-5/-6/-8/-11,IEC 61000-3-2/-3 |
| Marking and certifications |
CE,TÜV/GS,UL,cUL,C-Tick |
| Design and manufacture |
ISO 9001 |
| Dimensions (HxWxD in mm) and Weight (Kg) |
| UPS (electronics +battery)Tower |
235.5x145x400 |
235.5x145x400 |
235.5x145x505 |
| Rack |
NA |
88(2U) x 482.6 x 430 |
88(2U) x 482.6 x 493 |
| Electronics module Tower/Rack |
10/NA |
12/16 |
15/20 |
| Battery module Pulsar EXB Tower/Rack |
NA |
15/21 |
21/27.5 |
| CLA module (without batteries)Tower/Rack |
|
|
8.5/11.5 |
| Warranty |
2 years,extendable by contract |
| Pulsar |
2000 VA |
3000 VA |
| General |
| Power |
2000VA/1330W |
3000VA/2000W |
| Input-voltage range |
84/120/160 to 265 without using battery power |
| Frequency range |
50/60 Hz |
| Power factor (THDI) |
0.99 (< 5%) |
| Sinusoidal output voltage |
200/208/220/230/240 Volts |
| Harmonic distortion |
< 3% for linear loads, < 5% for non-linear loads |
| Efficiency On-line mode |
89% |
90% |
| Crest factor |
3.1 |
3.1 |
| Short circuit current |
27 |
41 |
| Overload capacity (on-line mode) |
130% for 60s, 160% for 10s, 250% for 1s |
| Batteries |
| Standard backup time |
|
| 100% rated output |
9 min |
9 min |
| 50% rated output |
20 min |
20 min |
| EXB battery extension module: |
|
| LA |
20 min |
20 min |
| XLA |
36 min |
36 min |
| 2XLA |
66 min |
66 min |
| Communication |
1 RS232/U-Talk port + 1 communication slot |
| Optional cards for UPS or MultiSlot module |
- XML-Web
- SNMP/Web
- 2 RS232 U-Talk or Basic (volt-free contacts) ports RS232 or RS485 JBus/ModBus
- 6 relay contacts 250V 2A
- USB
- 2 RS232 COM ports (HID protocol)
- 2 AS400 (volt-free contacts) or/and remote shutdown ports
|
| Standards |
| Performance |
EN 50091-3 |
| Safety |
EN 50091-1, IEC 60950 |
| EMC |
EN 50091-2, EN 55022/B, EN 55011/B, IEC 61000-4, IEC 61000-3-2 |
| Marking and certifications |
CE, TÜV/GS, C-Tick |
| Design and manufacture |
ISO 9001, ISO 14001 |
| Dimensions (HxWxD in mm) and weight (in kg) |
| UPS and EXB or CLA module dimensions |
443 x 173 x 465 (tower) |
177 x 483 x 462 (rack) |
| UPS weight |
28 (tower) 31 (rack) |
33 (tower) 36 (rack) |
| EXB module weight |
|
|
| LA |
22 (tower) 25(rack) |
28 (tower) 31 (rack) |
| XLA |
36 (tower) 39 (rack) |
48 (tower) 51 (rack) |
| CLA module weight |
11 (tower) 14 (rack) |
11 (tower) 14 (rack) |
| Warranty |
2 years, extendable by contract |
|
|
|